Professional Manufacturer of Power Equipment & Power Automation Solutions

GWPR320-DIS Line Distance Protection Relay

Functions(ANSI) 21/21N 21FL 68 50/50N 51/51N 51V 67/67N 79 25 27 60 81L 49
Product Desc

GWPR320-DIS numerical Line Distance Protection Relay is independently developed and manufactured by GoWatron. It is specially designed for 35kV and below distribution lines with neutral ungrounded or resistance-earthed power systems. The device supports both on-site cabinet mounting and control room panel mounting, integrating comprehensive fault protection, fault location, three-phase auto-reclosing and four-remote functions (telemetry, telesignalling, telecontrol, teleregulation) into one single unit.

  • It is equipped with dual Ethernet ports and RS485 dual communication interfaces, compatible with most substation integrated automation systems.
  • Standard communication protocols: IEC 60870-5-103, IEC 60870-5-104, Modbus RTU/TCP. These protocols fully support uploading telemetry data, telesignalling status, fault records and protection settings.
  • Optional communication protocol: IEC 61850 (supports MMS and GOOSE), which satisfies the networking requirements of intelligent digital substations.
Accuracy
Accuracy
≤ 0.2%
Quick Response
Quick Response
≤ 100ms
Reliable Protection
Reliable Protection
Comprehensive Protection
Quality Assurance
Quality Assurance
ISO 9001 Certified
Technical Support
Technical Support
24/7 Expert Support
Fast Delivery
Fast Delivery
Global Shipping
Warranty
Warranty
2-Year Warranty

Protection Functions

 Distance Protection (ANSI 21 Series)

  • (ANSI 21) Phase Distance Protection: Three-zone quadrilateral offset impedance (Zone Ⅰ/Ⅱ/Ⅲ), fitted with a positive-sequence directional element to eliminate the zone outlet dead zone. It adopts built-in 150ms temporary enable logic coordinated with out-of-step blocking to avoid maloperation.
  • (ANSI 21N) Ground Distance Protection: Three-zone ground offset impedance protection with zero-sequence reactance elements, which suppress protection overreach induced by transition resistance during single-phase earth faults.
  • (ANSI 21FL) Fault Locator: The location error for metallic short-circuit faults is limited to ±2%, enabling fast and precise fault point identification along transmission lines.
  • (ANSI 68) Out-of-Step Blocking Protection: Adopts dual judging criteria: impedance change rate dZ/dt and asymmetric fault enable logic. It blocks Zone Ⅰ and Ⅱ distance protection during system oscillation, while reliably tripping for internal faults.
  • Auxiliary high-speed acceleration logic: Asymmetrical successive acceleration and double-circuit successive acceleration, both capable of accelerating Zone Ⅱ distance tripping.

 Phase Overcurrent Protection (ANSI 50/51/67 Series)

  • (ANSI 50) Instantaneous Overcurrent Protection: Zone Ⅰ instantaneous phase fault protection, clears near-end phase faults within ms.
  • (ANSI 51) Definite-Time Phase Overcurrent Protection: Graded time-delay protection for Zone Ⅱ and Zone Ⅲ. Current threshold and delay time can be set independently to realize selective coordination between upstream and downstream protections.
  • (ANSI 51I) Inverse-Time Phase Overcurrent Protection: Compatible with standard, very inverse and extremely inverse-time characteristic curves for time grading coordination in multi-level distribution networks.
  • (ANSI 67) Directional Phase Overcurrent Protection: Adopts 90° phase-shift connection directional logic. It blocks protection against reverse faults to prevent mal-tripping caused by external faults.
  • (ANSI 51V) Voltage-Restrained Overcurrent Protection: Blocks overcurrent protection under motor back-feed and no-load operating conditions to eliminate maloperation risks.

Zero-Sequence Earth Fault Protection (ANSI 50N/51N/67N Series)

  • (ANSI 50N) Instantaneous Zero-Sequence Overcurrent Protection: Zone Ⅰ instantaneous earth fault protection for rapid isolation of near-end single-phase earth faults.
  • (ANSI 51N) Definite-Time Zero-Sequence Overcurrent Protection: Time-delayed earth fault protection for Zone Ⅱ and Zone Ⅲ, applicable to high-resistance earth faults on long-distance overhead lines.
  • (ANSI 51NI) Inverse-Time Zero-Sequence Overcurrent Protection: Dedicated inverse-time characteristics for earth faults, achieving sequential coordination of earth fault protection on segmented lines.
  • (ANSI 67N) Directional Zero-Sequence Overcurrent Protection: Direction discrimination based on self-residual voltage (3U0), reliably blocking protection responses to external earth faults.

Auto-Reclosing & Fault Acceleration (ANSI 79/25)

  • (ANSI 79) Three-Phase Single-Shot Auto-Reclosing: Dual trigger modes: protection tripping trigger / circuit breaker position mismatch trigger. It features a 15s charging cycle. The reclosing circuit will discharge and lock out under the following conditions: spring energy storage incomplete, control circuit disconnection, external blocking signal input.
  • (ANSI 25) Synchronism Check / Dead Bus Check Closing: Four configurable closing modes: Non-synchronism, Synchronism Check, Dead Bus Check, Synchronism + Dead Bus Check.
  • Auxiliary acceleration functions: Manual close fault acceleration; switchable pre-acceleration / post-acceleration mode. Independent current thresholds and delay settings are available for phase and zero-sequence acceleration zones.

Voltage & Frequency Stabilization Control and Circuit Supervision (ANSI 27/60/81L)

  • (ANSI 27) Under-Voltage Load Shedding Protection: Triggers time-delayed load shedding when three-phase voltage falls below the set threshold. Equipped with dual blocking logics based on voltage change rate and negative-sequence voltage to prevent false tripping.
  • (ANSI 60) VT Fuse Failure Supervision: Automatically detects three-phase voltage loss, single/two-phase VT disconnection and generates active alarm signals. Users may selectively disable all directional and voltage-restrained protection functions upon detection.
  • (ANSI 81L) Under-Frequency Load Shedding Protection: Automatically sheds loads when system frequency drops below threshold. Triple blocking criteria (rate of change of frequency (df/dt), undervoltage, line active load) distinguish genuine power shortage from transient fault conditions.

 Load Supervision & Device Self-Check (ANSI 49)

  • (ANSI 49) Overload Protection: Monitors three-phase overload current exceeding set value, supporting two output modes: Alarm Only or Time-Delayed Trip.
  • Hardware self-check function: Uploads real-time alarm information for RAM/ROM/AD sampling errors, invalid protection settings, output loop failures and dual communication port malfunctions.

Core Technical Parameters

  • Power Supply: DC 110V/220V, AC 220V (configurable on order)
  • AC Analog Input: CT secondary rated current 1A / 5A; VT line voltage 100V; Rated frequency 50Hz
  • Measurement Accuracy: Class 0.2 for voltage and current; Class 0.5 for active/reactive power and electrical energy
  • Operating Speed: Operating time ≤40ms at 1.2 times the instantaneous zone setting
  • Fault Location Precision: Metallic fault positioning error ≤±2%
  • Timing Accuracy: Max error ≤25ms for delays ranging 0~1s; Max error ≤±2.5% for delays over 1s

 Application Scenarios

  • Applicable Voltage Level: Medium and low-voltage distribution lines of 35kV and below
  • Applicable Power Grid: Neutral ungrounded distribution system, resistance-earthed distribution system
  • Applicable Line Types: Single-circuit distribution feeders, double-circuit parallel feeders
  • Installation Methods: On-site cabinet mounting, centralized panel mounting in substation control room
  • Application Sites: Urban and rural distribution substations, industrial and mining power distribution rooms, park integrated automation power distribution cabinets, digital intelligent substations (requires optional IEC 61850 module)
REQUEST QUOTE(RFQ)
Please fill in the form below and we will get back to you within 24 hours.
Quote Form

1.PROJECT INFORMATION

2. PRODUCTS FOR QUOTATION


3. RFQ SCHEDULE

4. TECHNICAL DOCUMENTS UPLOAD

Supported formats: PDF, Word, Excel, CAD, ZIP, RAR, JPG, PNG
Max file size: 50MB per file | Max total size: 200MB


5. PROJECT REQUIREMENTS


6.CONTACT INFORMATION


6. VERIFICATION


GWPR320-DIS Line Distance Protection Relay Front View
GWPR320-DIS Line Distance Protection Relay Side View
GoWatron WhatsApp contact icon GoWatron email contact icon GoWatron phone contact icon
Insert math as
Block
Inline
Additional settings
Formula color
Text color
#333333
Type math using LaTeX
Preview
\({}\)
Nothing to preview
Insert