GWPR-SRI Reactor Integrated Differential Protection Relay
Product Desc
GWPR-SRI Reactor Integrated Differential Protection Relay (Brand: GoWatron) is suitable for reactor protection and measurement & control at voltage levels of 132 kV, 66 kV, 33 kV, and 11 kV. It uses a 32-bit high-performance microcontroller integrating DSP and FPU, providing comprehensive protection, measurement, control, communication, and time synchronisation functions. The GWPR-SRI Reactor Integrated Differential Protection Relay features flexible hardware configuration and high immunity to electromagnetic interference, meeting the diverse requirements of power systems for reactor protection.
- Communication Interfaces: 2 Ethernet ports, 2 RS-485 ports (the second RS-485 port is multiplexed with the time synchronisation port; communication and time synchronisation are selected via configuration)
- Communication Protocols: IEC 60870-5-104, IEC 60870-5-103, IEC 61850 (optional)
- Time Synchronisation Methods: Communication message-based time synchronisation, SNTP time synchronisation, and IRIG-B time synchronisation
Accuracy
≤ 0.2%
Quick Response
≤ 100ms
Reliable Protection
Comprehensive Protection
Quality Assurance
ISO 9001 Certified
Technical Support
24/7 Expert Support
Fast Delivery
Global Shipping
Warranty
2-Year Warranty
1. Product Introduction
- The GWPR-SRI Reactor Integrated Differential Protection Relay is a reactor integrated differential protection relay developed by GoWatron, suitable for reactor protection and measurement & control at voltage levels of 132 kV, 66 kV, 33 kV, and 11 kV. The GWPR-SRI Reactor Integrated Differential Protection Relay adopts a full-panel, fully enclosed chassis with isolation between power/control circuits and low-level signal circuits, and corresponding anti-interference measures are taken in both software and hardware design, meeting relevant electromagnetic compatibility standards. The GWPR-SRI Reactor Integrated Differential Protection Relay provides complete protection functions, with each protection element designed in a modular manner, mutually independent and flexibly configurable, featuring a user-friendly human-machine interface and convenient on-site testing functions.
- The GWPR-SRI Reactor Integrated Differential Protection Relay supports 21 active binary inputs, 11 protection outputs, 2 signal outputs, and 1 device power-loss output. It is equipped with dual Ethernet interfaces, RS-485 serial communication interfaces, and an IRIG-B time synchronisation interface. The GWPR-SRI Reactor Integrated Differential Protection Relay uses independent 16-bit analogue-to-digital conversion for high-precision sampling, combined with an algorithm for filtering anomalous samples to improve the anti-interference capability of AC signal acquisition. It also features fault recording, event logging, and communication with the supervisory system, facilitating on-site commissioning, operation, and maintenance.
2. Product Functions
Differential Protection
- (ANSI 87R) Instantaneous Differential Protection (Trip) — Fast differential protection for internal reactor faults
- (ANSI 87R) Percentage-Restrained Differential Protection (Trip) — Percentage restrained differential protection
- CT Circuit Supervision (Immediate indication with a time-delayed alarm) — CT secondary circuit abnormality supervision
- Differential Current High Alarm — Differential current over-limit supervision
Overcurrent Protection
- (ANSI 50/51) Three-stage Definite-Time Overcurrent Protection (Trip, with configurable directional and composite voltage supervision) — Definite-time overcurrent protection; when directional supervision is enabled, the protection operates as directional overcurrent protection (ANSI 67)
- (ANSI 51) Inverse-Time Overcurrent Protection (Trip, selectable among standard inverse, very inverse, and extremely inverse, with configurable directional and composite voltage supervision) — Inverse-time overcurrent protection; when directional supervision is enabled, the protection operates as directional overcurrent protection (ANSI 67)
- (ANSI 49) Overload Protection (Alarm/Trip selectable) — Reactor overload supervision and protection
- (ANSI 46) Negative-Sequence Overcurrent Stage I (Trip) — Negative-sequence current/phase current unbalance protection
- (ANSI 46) Negative-Sequence Overcurrent Stage II (Alarm/Trip selectable)
- (ANSI 50N/51N) Zero-Sequence Overcurrent Stages I & II (Trip) — Zero-sequence definite-time overcurrent protection
- (ANSI 50N/51N) Zero-Sequence Overcurrent Stage III (Alarm/Trip selectable)
- (ANSI 51N) Zero-Sequence Inverse-Time Overcurrent Protection (Trip)
- (ANSI 50/51) Neutral-End Overcurrent Stages I & II (Trip, with configurable composite voltage supervision) — Definite-time overcurrent protection for reactor neutral-end current
Voltage Protection
- (ANSI 59) Overvoltage Protection (Trip) — Overvoltage protection
- (ANSI 27) Undervoltage Protection (Trip) — Undervoltage protection
- System Power Loss Protection (Alarm/Trip selectable) — Identifies system power-loss status based on specified voltage, current, and status criteria
- PT Circuit Supervision (Alarm) — Voltage transformer secondary circuit abnormality supervision
Other Protection
- Control Circuit Disconnection Supervision (Alarm) — Circuit breaker control circuit abnormality supervision
- 6 Channels of Non-Electrical Protection (Alarm/Trip selectable) — Receives contact signals from reactor body protection
Measurement and Control Functions
- AC Signals: Voltages Ua, Ub, Uc, Uab, Ubc, Uca; Currents Ia, Ib, Ic, ia1, ib1, ic1, ia2, ib2, ic2, i30
- Power: P, Q, COSΦ
- Energy: EP+, EP-, EQ+, EQ-
- Supports 21 active binary inputs (AC/DC 220 V, DC 100 V, or DC 48 V; please specify when ordering)
- Supports 11 protection outputs, 2 signal outputs, and 1 device power-loss output
3. Product Application Scenarios
- The GWPR-SRI Reactor Integrated Differential Protection Relay is suitable for the following scenarios:
- Reactor protection and measurement & control at voltage levels of 132 kV, 66 kV, 33 kV, and 11 kV
- Reactor protection in substations, power plants, industrial and mining enterprises, and other power systems
- Applications requiring multiple protection functions such as differential protection, overcurrent protection, zero-sequence protection, and overvoltage/undervoltage protection
- Power automation systems requiring integrated measurement & control, communication networking, and time synchronisation
- Smart substations requiring flexible protection function configuration and support for IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 (optional) communication protocols
- Applications requiring real-time monitoring, fault recording, and event logging of reactor operating status
- Operation and maintenance scenarios requiring on-site commissioning, local testing, and report printing