GWPR300-T Station Transformer Protection Relay
Product Desc
The GWPR300-T Station Transformer Protection Relay is an integrated protection, measurement and control device suitable for station service transformers, earthing transformers and similar equipment in 132 kV and 66 kV substations. The device uses a high-performance 32-bit microcontroller with integrated DSP and FPU capabilities, and features comprehensive protection functions, high-precision sampling, a user-friendly human–machine interface and multiple communication interfaces. It integrates protection, measurement, control, communication, fault recording and printing functions, and is widely used in substation automation systems for station service transformers and earthing transformers.
Communication Functions
- 2 Ethernet ports (supporting IEC 60870-5-104)
- Optional IEC 61850 support via the 2 Ethernet ports
- 1 RS-485 communication port (supporting Modbus RTU)
- Supports time synchronisation via communication protocol messages, SNTP and IRIG-B
Accuracy
≤ 0.2%
Quick Response
≤ 100ms
Reliable Protection
Comprehensive Protection
Quality Assurance
ISO 9001 Certified
Technical Support
24/7 Expert Support
Fast Delivery
Global Shipping
Warranty
2-Year Warranty
1. Product Introduction
- The GWPR300-T Station Transformer Protection Relay is a multifunctional device integrating protection, measurement and control for station service transformers, earthing transformers and similar equipment in 132 kV and 66 kV substations. The device uses a high-performance 32-bit microcontroller with integrated DSP and FPU capabilities for protection calculations, output logic processing, event recording, fault recording and communication with the supervisory system. The hardware uses independent 16-bit analogue-to-digital converters for high-precision sampling, together with an algorithm for filtering abnormal sample values to improve immunity to interference during AC signal acquisition.
- The GWPR300-T Station Transformer Protection Relay provides comprehensive protection functions. Each protection element is modular, independent and flexibly configurable. The device features a user-friendly human–machine interface and convenient on-site testing functions. It is equipped with dual Ethernet ports, an RS-485 serial communication port and an IRIG-B time synchronisation port to support integration into various automation systems.
Main technical features:
- High-performance 32-bit microcontroller with integrated DSP and FPU capabilities
- Independent 16-bit analogue-to-digital converters for high-precision sampling and high immunity to interference
- Modular protection design with independently configurable protection elements
- Fully enclosed chassis with an integrated front panel and strict separation between power circuits and low-level signal circuits
- Supports dot-matrix printers for printing settings, event records and fault records
2. Product Functions
Overcurrent Protection
- (ANSI 50/51) Three-stage overcurrent protection (trip, with configurable definite-time delays and optional composite voltage supervision)
- (ANSI 51) Inverse-time overcurrent protection (trip, with selectable standard inverse, very inverse and extremely inverse characteristics and optional composite voltage supervision)
- (ANSI 49) Overload protection (alarm/trip selectable)
- (ANSI 51G) Stage I zero-sequence overcurrent protection (trip, with zero-sequence voltage blocking)
- (ANSI 51G) Stage II zero-sequence overcurrent protection (trip, with zero-sequence voltage blocking)
- (ANSI 51G) Stage III zero-sequence overcurrent protection (alarm/trip selectable)
- (ANSI 51G) Stage I low-voltage-side zero-sequence overcurrent protection (trip)
- (ANSI 51G) Stage II low-voltage-side zero-sequence overcurrent protection (trip)
- (ANSI 51G) Stage III low-voltage-side zero-sequence overcurrent protection (alarm/trip selectable)
Negative-Sequence Protection
- (ANSI 46) Stage I negative-sequence overcurrent protection (trip, for excessive negative-sequence current caused by phase loss or other abnormal conditions)
- (ANSI 46) Stage II negative-sequence overcurrent protection (alarm/trip selectable, for protection against current unbalance)
Voltage Protection
- (ANSI 59) Overvoltage protection (trip)
- (ANSI 27) Undervoltage protection (alarm/trip selectable)
- (ANSI 59N) Residual overvoltage protection (alarm/trip selectable)
Monitoring and Alarms
- VT (PT) circuit failure alarm (supervision of voltage circuit abnormalities)
- Trip circuit supervision alarm
System Protection
- System loss-of-supply protection (alarm/trip selectable, combining undervoltage and no-current criteria)
Non-Electrical Protection
- (ANSI 63) Main transformer door-open protection (alarm/trip selectable)
- (ANSI 71) Load control (alarm/trip selectable)
- (ANSI 71G) Buchholz relay alarm input (gas accumulation alarm)
- (ANSI 71G) Buchholz relay trip input (oil surge trip)
- (ANSI 26/49) Temperature-rise protection (alarm/trip selectable)
- (ANSI 26/49) Overtemperature protection (alarm/trip selectable)
- Non-electrical protection 1 (alarm/trip selectable; ANSI number depends on the connected signal type)
- Non-electrical protection 2 (alarm/trip selectable; ANSI number depends on the connected signal type)
Measurement and Control Functions
- Voltage measurement: Ua, Ub, Uc, Uab, Ubc, Uca, 3U0, U0z
- Current measurement: Ia, Ib, Ic, ia, ib, ic, 3i0, i0z, 3i0L
- Power measurement: P, Q, cosφ
- Energy metering: EP+, EP−, EQ+, EQ−
- Supports 21 active binary inputs (AC/DC 220 V, DC 110 V or DC 48 V; to be specified when ordering)
- Supports 13 independent relay outputs and 1 device loss-of-supply signalling output
Printing Function
- Supports dot-matrix printers via a serial interface for printing settings, event records and fault records
Recording Functions
- Protection events: records the time, operating value and protection function name for each protection operation, with a capacity of up to 128 records
- Alarm events: records the time, operating value and alarm name for each alarm event, with a capacity of up to 128 records
- Communication events: records changes in communication status, with a capacity of up to 128 records
- Operation records: records user operations, including setting changes and the enabling or disabling of protection functions, with a capacity of up to 128 records
- Self-check events: records events generated by the device self-check functions, with a capacity of up to 16 records
- Fault records: records waveforms associated with protection operations, with a capacity of up to 32 records
3. Application Scenarios
- Protection, measurement and control of station service transformers in 132 kV and 66 kV substations
- Protection, measurement and control of earthing transformers
- Integrated protection, measurement and control for station service transformers and earthing transformers
- Distribution systems requiring overcurrent, overload, negative-sequence, zero-sequence, overvoltage and undervoltage protection
- Applications requiring integration into substation automation systems via IEC 60870-5-104, IEC 61850 (optional) or Modbus RTU
- Substation automation projects requiring fault recording, event recording and printed reports
- Industrial installations requiring dual Ethernet ports, RS-485 communication and an IRIG-B time synchronisation interface